MSI has a long history of working with reciprocating machinery. This case history is based on a project from 2003, so some of the figures may appear dated.
Like many troubleshooting projects, this issue could have been resolved more quickly and efficiently if MSI's motion magnification video technology, VibVue®, had been available in 2003.
An acoustic resonance was the suspected root cause for excessive piping vibration in a high-value CO2 application. Fortunately, specialized testing by MSI efficiently identified that high discharge pressure pulsations interacting with a discharge pipe structural natural frequency (i.e., resonance) was the primary problem root cause. Most importantly, MSI was able to recommend a practical fix to the potentially dangerous problem.

Figure 1: Top - Cylinder 1 discharge pressure fluctuations measured using dynamic pressure transducers was 12 psi peak to peak oscillation. Bottom - most of it at a 6 Hz frequency (1 times running speed) and 12 Hz.

Figure 2: Discharge pipe elbow Frequency Response Function (FRF) plot of the Experimental Modal Analysis (or impact) test MSI performed while the compressor was operating. The peak near at 6 Hz indicates a structural natural frequency which was also confirmed with Operating Deflection Shape (ODS) testing.

Figure 3: Discharge pipe elbow vibration was excessive due to a structural vibration response (over 10 mils) to the high 12 psi Cylinder 1 pressure pulsation at 6 Hz. This data is plotted logarithmically so that resonance peaks are evident in the spectrum “noise floor.” The broadband peaks near 6 Hz and 30 Hz further confirm the Figure 2 experimental modal analysis (i.e., impact) test results – that the large pipe motion is due to structural pipe resonance.
Install targeted discharge piping supports at MSI specified locations to detune resonance, and optionally increase discharge bottle size to reduce pulsation amplitude.
Excessive vibration in reciprocating compressors is commonly caused by:
Pressure pulsations with high harmonic content
Structural resonance in piping systems
Insufficient or degraded piping supports
Mechanical looseness in compressor components
In this case, high discharge pulsations exciting a discharge pipe elbow structural resonance frequency was the primary driver—not acoustic amplification.
Operational vibration measurements across:
Cylinders
Baseplate and foundation
Piping systems
Flowmeter
Experimental Modal Analysis (or impact) testing while the compressor operated to identify natural frequencies
Dynamic pressure measurements using high-frequency transducers
Operating Deflection Shape (ODS) testing for visualizing vibration modes
ODS analysis allows engineers to:
The flowmeter experienced calibration drift due to:
Remember that Flowmeter calibration issues in reciprocating compressor systems can be caused by mechanically induced vibration rather than instrumentation faults.
No—acoustic resonance played a minor role.
Primary Root Cause
A combination of:
High discharge pressure pulsations
Structural resonance at natural frequencies
Secondary Contributors
Loose cylinder support
Inadequate piping support
System stiffness changes after refurbishment
1. Improve Structural Support
Reinforce existing supports
Add supports at high-motion
Focus on 6 Hz, 12 Hz, and 30 Hz response
2. Detune Resonance
Shift natural frequencies away from excitation frequencies
Add supports incrementally and monitor response
3. Address Mechanical Looseness
Inspect and tighten:
Cylinder 2 vertical support
Piping connections
4. Consider Larger Discharge Bottles
Reduce pressure pulsations
Improve long-term system stability
5. If a resonance issue is suspected use a combination of the specialized test methods discussed above to identify the problem root cause and Finite Element Analysis (FEA) methods to design and “test” the solution to avoid trial and error problem solving.
The main cause in this case is pressure pulsations interacting with structural natural frequencies, not acoustic resonance.
Typically running speed harmonics, such as 6 Hz, 12 Hz, and 30 Hz in this case.
By adding supports to shift natural frequencies (detuning) and reducing excitation forces.
Yes. Even moderate vibration (~1 mil) can cause calibration drift and measurement errors.
Not always, but they help reduce pulsation amplitude and improve long-term reliability.
MSI was recommended to analyze flood control pumping station system dynamics, including evaluation of the platform design with regard to vibration.
A contractor putting together a water treatment facility encountered vibration issues with various pumps during commissioning.
A county water treatment plant heard “cavitation-like noise” from their newly installed pumps and called MSI for help.
MSI consultants solve difficult or urgent problems of vibration in machinery, taking into account the performance process parameters in critical rotating machinery and systems. MSI’s right-first-time, high-value solutions and clear reports are based on a 30-year track record of reliably solving the problem.
Copyright © 2025 Mechanical Solutions. All rights reserved. Privacy Policy